14
ICE MACHINE HEAT OF REJECTION
Heat of Rejection*
Air Conditioning** Peak
1,145 2,300
* B.T.U./Hour
** Because the heat of rejection varies during the
ice making cycle, the figure shown is an
average.
Ice machines, like other refrigeration equipment, reject
heat through the condenser. It is helpful to know the
amount of heat rejected by the ice machine when
sizing air conditioning equipment where self-contained
air-cooled ice machines are installed.