124 Part Number 80-1230-9 10/10
The SafeGuard will be automatically erased from
memory and the Water Level Probe light will not flash.
No Water Checklist
Possible Problem List Corrective Action List
No water Restore water supply.
Quick disconnect removed
from water float valve
Restore water supply.
Water float valve screen
blocked
Clean screen.
Water float valve solenoid
coil defective
Replace coil (see Water
float valve diagnostics).
Water float valve improperly
adjusted
Adjust valve (see Water
level check).
Dump valve leaking
Repair or replace dump
valve.
Water level probes
disconnected or removed
Connect and correctly
position probes.