–31–
Q1400C/SU1000C
1. Check the water level while the ice machine is in
the Clean mode and the water pump is running.
The correct water level above the water pump
impeller housing is:
Q1400C - 1/8-1/2 in. (3-12.5 mm)
SU1000C - 1/8-1/4 in. (3-6.35 mm)
2. The float valve is factory-set for the proper water
level. If adjustments are necessary:
A. Loosen the two screws on the float valve
bracket.
B. Raise or lower the float valve assembly as
necessary, then tighten the screws.
If further adjustment is required, carefully bend the
float arm to achieve the correct water level.
WATER
LEVEL