214 Part Number 80-1230-9 6/08
NOTE: Perform Steps 1 and 2 before performing this
step.
A. Disconnect the load from the output relay
terminals.
B. Reconnect the sensor leads and supply
power to the control.
C. Replace the cover.
D. Check the control settings for proper values.
E. Press and hold MENU until SP appears.
F. Press up and down (arrows) to change the
setpoint temperature above and below the
sensor temperature until the relay energizes
and de-energizes.
G. If the output relay does not perform as
indicated replace the control.
H. If proper operation of the control is verified,
reconnect the load.